Buy 5 or More Units - Unlock Priority Discounts!
Buy 20 or More Units - Get Exclusive Volume Discounts!
Also Support:
Are you a reseller or placing a large order?
We're happy to offer Special Pricing tailored to your needs.
Click "Request Quote" or email us at [email protected]
to get your best price today!
Product Code: VFQD-025
MPN #: 60229
When a motor-driven machine needs controlled speed, torque, acceleration, and stopping, connecting the motor directly to a fixed-frequency supply can limit how precisely the equipment can operate. A variable frequency drive provides adjustable motor control while also offering communication, PLC, braking, monitoring, and protection functions within the drive.
The Beijer BFI-P2-44-0460-3F4N-MN is an IP55 AC variable frequency drive designed to control three-phase AC motors with a rated motor current of 46 A and motor power of 22 kW. It converts the incoming 380–480VAC supply into controlled motor output, allowing motor speed and operating behavior to be adjusted according to the application.
The drive supports several motor types, including three phase AC induction (IM), AC permanent magnet (PM), Brushless DC (BLDC), and Synchronous reluctance (SynRM). Its control modes include V/F Voltage Vector, Sensorless Vector Speed Control, Sensorless Vector Torque Control, Closed Loop Speed Control, Closed Loop Torque Control, and other specified motor control methods, providing different approaches for controlling motor operation.
For applications where acceleration, stopping, and braking need to be managed, the drive provides adjustable ramp-to-stop, fast stop, coast-to-stop, motor flux braking, and a built-in braking transistor. Torque and current limitation, skip frequency, and adjustable PWM frequency further support controlled motor operation. The drive can also provide regenerative capacity at 100 % ED.
The BFI-P2-44-0460-3F4N-MN includes Modbus RTU and CANopen communication, while several industrial Ethernet and fieldbus protocols are available as external options. Its digital and analog setpoint options allow speed or control references to be supplied through voltage, current, fixed speeds, motorised potentiometer, internal PLC, keypad, and supported communication interfaces.
The IP55 enclosure is designed for installations where protection from dust and water is required. The drive also includes a built-in PLC, master/slave speed control, advanced hoist control, PID control with sleep/wake functionality, programmable display, safety inputs, Safe Torque OFF, fault memory, data logging, and service-life monitoring. CE, UL, cUL, DNV, and the specified safety and compliance standards support its use in industrial and marine applications.
| General description | |
| Article number | 60229 |
| Warranty | Up to 2 years |
| Mechanical | |
| IP class | IP55 |
| Physical size | Size 4 |
| Measurements (H x W x D) | 450 mm x 171 mm x 252 mm |
| Weight | 12 kg |
| Typical power loss at rated power | 2 % of rated power |
| Main switch | Yes, as option |
| Built in Main switch, control switch and potentiometer | No |
| Conformal coated PCBs | Yes, IEC 60721-3-3, 3S3/3C3 |
| Output ratings | |
| Output voltage | 3 x 400 VAC |
| Rated motor current | 46 A |
| Overload capacity | 150% for 60 seconds, 200% for 4 seconds |
| Motor power | 22 kW |
| Output frequency | 0 – 500Hz, 0.1Hz resolution |
| Supported motor types | 3 phase AC induction (IM), AC permanent magnet (PM), Brushless DC (BLDC), Synchronous reluctance (SynRM) |
| Built-in brake transistor | Yes |
| Regenerative capacity | 100 % ED |
| Input ratings | |
| Supply voltage | 380 – 480VAC ± 10% |
| Voltage fluctuations | +/- 10% |
| Phase imbalance | 3% maximum allowed |
| Displacement factor | > 0.98 |
| Supply frequency | 48 – 62Hz |
| Power cycles | 120 per hour maximum, evenly spaced |
| Control specification | |
| Current/torque limitation | Torque and current limitation |
| PWM frequency | 4-32 kHz effective |
| Stopping mode | Ramp to Stop: User Adjustable 0.1 – 6000 seconds. Fast stop. Coast to Stop |
| Braking | Motor Flux Braking, Built-in Braking Transistor |
| Skip frequency | Yes |
| Analog setpoint control | 0 to 10V, 10 to 0V, −10 to 10V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
| Communication | |
| Modbus RTU | Yes, 9.6 - 115.2 kbps (8N1, 8N2, 8E1, 8O1) |
| BACnet MS/TP | No |
| Modbus TCP | Yes, external option |
| Ethernet IP | Yes, external option |
| EtherCat | Yes, external option |
| Profinet IO | Yes, external option |
| Profibus DP(DPV1) | Yes, external option |
| Device Net | Yes, external option |
| CC-Link | Yes, external option |
| CAN open | Yes, 125-1000 kbps |
| Display | |
| Programmable display | Yes |
| Multi language OLED display | TFT Display |
| External OLED display | Yes, TFT Display |
| LED display | No |
| HVAC | |
| PID-control | Yes with sleep/wake up functionality |
| Spin start | Yes |
| Pump dry protection | No |
| Pump prime and burst protection | No |
| Stir function | No |
| Motor pre-heat | No |
| Broken impeller and broken belt detection | No |
| Automatic cleaning for pumps | No |
| Bypass control | Yes |
| Fire mode | No |
| Control terminals | |
| Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
| Inputs | 5 in total, 3 Digital, 2 Analog or Digital, selectable |
| Digital inputs | 10-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
| Analog inputs |
Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
| Outputs | 4 total, 2 relays, 2 analog or digital |
| Digital transistor outputs | 24VDC/20 mA, Internal supply |
| Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 5A AC, 5A DC |
| Analog outputs | 0 to 10 Volt, 0 to 20mA, 4 to 20mA |
| Safety inputs | 2 |
| Extra IOs | Yes, internal option |
| Control features | |
| Speed control Master/slave | Yes, Master and slave |
| Modbus master functionality | Yes, Master and slave |
| Advanced hoist control | Yes |
| Built-in PLC | Yes |
| Standard compliances | |
| Low voltage directive | 2014/35/EU |
| EMC directive | 2014/30/EU |
| Conformance | CE, UL, cUL |
| Machine directive | 98/37/EC |
| Marine approvals | DNV |
| Safe torque OFF | Cat 3/PL"d" According to ISO 13849-1, SIL CL 2 According to EN61800-5-2 / EN62061 / IEC61508 |
| Restriction of hazardous substances | RoHS2 |
| Registration evaluation and authorisation of chemicals | Reach |
| Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
| DC Bus discharge time | EN 61800-5-1:2007 |
| Electrostatic discharge | EN 61800-3:2004+A1-2012. Test techniques EN 61000-4-2:2009. |
| Dielectric strength | 61800-5-1: 2007 |
| Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
| Electrical fast transient burst | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-4:2004. |
| Ambient conditions | |
| Temperature operation | -10 to 40 °C |
| Humidity | 95% max, non-condensing |
| Maintenance | |
| Fault memory | Last 4 Trips stored with time stamp |
| Data logging | Logging of data prior to trip, Current, Temperature, DC Bus Voltage |
| Maintenence indicator | Yes. Onboard service life monitoring |
| Monitoring | Hours Run Meter, kWh/MWh meter |
No Attachments Found!
Be the first to write a review
We are retiring PICOPC Products MNHO-073, MNHO-048 and MNHO-043 and they have reached EOL (End Of Life) as we are introducing new products with better technology. We would recommend you to look into MNHO-095. For Untangle, pfSense, OPNsense, Windows 11, Proxmox VE etc. we recommend MNHO-095 whereas for Sophos, Kerio Control and Endian, we would recommend MNHO-069. (A complete list of supported OS can be found in each product's listing)